Basic Parameters |
Dimensions |
Single power module: 700 mm x 246 mm x 152 mm Single battery module: 700 mm x 390 mm x 158 mm |
|
weight |
Approx. 17 kg for a single power module Approx.50 kg for a single energy storage module |
|
|
Installation Mode |
Wall-mounted/ground-mounted |
|
|
Degree of protection |
IP65 |
|
|
AC input |
Input voltage system |
Single-phase 200/208/220/230/240 VAC, 220 V AC by default |
|
Input voltage range |
20% |
|
|
Input current |
Max. 30 A |
|
|
Frequency |
50/60Hz |
|
|
lightning protection |
Differential mode: 3KA; common mode (two-wire pair PE): 5KA; 8/20 μs |
|
|
PV input |
Start-up voltage |
100V DC |
|
Maximum input voltage |
435V DC |
|
|
MPPT voltage range |
90-420V DC |
|
|
Rated input voltage |
345V DC |
|
|
Maximum input capacity of the MPPT |
5.5KWp |
|
|
PV string quantity |
2 strings |
|
|
Number of MPPT channels |
1 channel |
|
|
Maximum input current |
2*15A |
|
|
Maximum short circuit current |
2*18A |
|
|
lightning protection |
10 kA common mode (two-wire pair PE), 8/20 μs |
|
|
AC output |
Output voltage system |
Single-phase 200/208/220/230/240 VAC, 220 V AC by default |
|
Output frequency |
50/60 Hz. The default value is 50 Hz. |
|
|
Maximum output current |
30A |
|
|
Input and output power |
6kVA/5kW |
|
|
THD |
‚â§ 3% R load |
|
|
Bypass input power |
Maximum bypass input power |
6kW |
|
overload capacity |
102% ‚â§ Load ‚â§ 125% |
30S |
|
125% < Load ‚â§ 150% |
10s |
|
|
>150%/short circuit |
0.3S |
Specifications
|
Battery parameters |
Output input voltage |
370-480VDC |
|
Rated capacity 1 |
5 kWh per module |
|
|
Maximum capacity |
Single system scenario: max. support 6 pcs batteries, 5 kW output (5Kw@30kWh) |
|
|
Maximum output power |
2.5 kW per module |
|
|
cycle life |
6000 times @ 25°C, 80% DOD |
|
|
AC parallel box |
Dimensions (W x H x D) |
350 mm x 450 mm x 150 mm |
|
weight |
Approx. 12 kg |
|
|
Input voltage |
200/208/220/230/240 V AC. The default value is 220 V AC. |
|
|
Input current |
Maximum 90A |
|
|
Output voltage |
200/208/220/230/240 V AC. The default value is 220 V AC. |
|
|
Output current |
Max. 90A |
|
|
Cable outlet mode |
Bottom in and bottom out |
|
|
Installation Mode |
Wall-mounted or pole-mounted installation |
|
|
Degree of protection |
IP55 |
|
|
Environmental parameters |
Operating temperature |
0°C to 45°C (without +1120w/m^2 solar radiation) |
|
Transport temperature |
- 40°C -+ 70°C |
|
|
Storage temperature |
- 40°C -+ 70°C |
|
|
relative humidity |
5%-95% (RH) |
|
|
Altitude Requirements |
0~4000m (The operating temperature decreases by 1°C per 200m when the altitude is 2000 m to 4000 m.) |
|
|
Noise level |
When temperature is 30°C, the noise is ≤40 dBA@1 m. |